Tools

Diesel generator size calculator

Enter the loads that run at the same time and the largest motor you need to start. The calculator converts kW to kVA, allows for altitude and heat, adds a reserve, and shows which of our models cover the result. Every step is shown, so you can check the figures yourself.

Your loads and site

Results update as you type.

Loads

Everything that runs at the same time.

The pump, compressor or air conditioner with the highest rating. Leave 0 if there is none.

A motor draws 3 to 7 times its running power when it starts. Use 3 if you are not sure.

Electrical

0.8 is typical for mixed loads.

Site conditions

Above 1000 m the engine loses about 3% per 300 m.

Above 40 °C, about 2% less per 5 °C.

Room for loads you add later.

Result

Required generator size

14.4kVAprime power

Includes 15% reserve · 50 Hz · Single-phase

How we got there

1Running load
10 kW
2Peak load with motor start
10 kW
3In kVA at PF 0.8
12.5 kVA
4After altitude and heat derating (0%)
12.5 kVA
5With 15% reserve
14.4 kVA
Current at 230 V
62.6 A
Note: This is an estimate. Motor starting depends on the motor and how it is started. An engineer confirms the size from your actual loads before you order.

Want an engineer to check it against your actual loads?

Send these results to an engineer →WhatsApp

Models that cover this load

Prime power at 50 Hz, Single-phase. Standby power is higher. Size on prime for daily running.

How the calculator works

It follows the same five steps as our generator sizing guide. Add the loads that run together. Add the starting surge of the largest motor. Divide by the power factor to get kVA. Allow for altitude and heat. Then add a reserve for loads you will add later.

The altitude rule is about 3% less output for every 300 m above 1,000 m. The heat rule is about 2% for every 5 °C above 40 °C. Both come from our guide to diesel derating at altitude.

Prime or standby?

The models shown are matched on prime power, the rating for daily running. Standby power is about 10% higher and is meant for emergency use only. If the set will run every day, size on prime. Our guide on prime and standby power explains the difference.

Want the whole chart?

The kVA size chart lists common loads with their kW, kVA and current, so you can check a result against typical equipment.

Questions

How do I convert kW to kVA?
Divide kW by the power factor. At a power factor of 0.8, 16 kW is 20 kVA.
How much bigger should the generator be than my load?
Size for the peak, including the largest motor start, then add 10 to 20% reserve. At altitude or in heat, size for the derated output.
Why does a pump need a bigger generator than its rating?
A motor draws 3 to 7 times its running power for a moment when it starts. The generator has to supply that peak without the voltage collapsing.