What Is an ATS for a Diesel Generator? (And When You Actually Need One)

An ATS starts the generator and moves the load when the mains fails — unattended. It is not a UPS: there is still a gap of seconds you have to plan for.

Reviewed by Jim Yue, Head of Supply Chain

An ATS (automatic transfer switch) monitors the mains supply. When the mains fails, it starts the generator and moves the load to it. When the grid returns, it moves the load back. No one needs to be on site. Depending on the market, the device is called an automatic transfer switch (ATS), a transfer panel or a changeover panel. Without one, someone has to walk to the machine, start it and operate a changeover switch by hand. That difference decides whether a standby set is worth owning at an unmanned site.

What happens, second by second

The sequence is always the same. Knowing it avoids the most common false expectation:

  1. The mains fails. The ATS confirms a real outage, not a brief flicker. The confirmation delay is typically 1–3 seconds.
  2. Start signal. The controller cranks the engine. A healthy set starts within a few seconds.
  3. Warm-up. The set runs without load until voltage and frequency are stable, usually 5–15 seconds.
  4. Transfer. The load moves from the mains to the generator.
  5. The grid returns. The ATS waits until the grid is stable, often 1–3 minutes, and transfers the load back. The engine then runs without load to cool down before it stops.

The total time from outage to restored power is typically 10–30 seconds. That is fast enough for lighting, pumps, refrigeration, workshops and most commercial loads.

What an ATS does not do

An ATS is not a UPS. Those 10–30 seconds are a real outage at the socket. Equipment that cannot tolerate a break needs a UPS to bridge the gap: servers, network equipment, medical equipment, PLCs in mid-cycle and point-of-sale terminals. The generator behind the UPS then carries the load for the long run. A UPS and an ATS work together; one does not replace the other.

The second limit is mechanical: an ATS needs an electric-start engine and a charged battery. A recoil-start set cannot be automated, because the controller has nothing to operate. For this reason, automatic operation is available on electric-start models only.

Do you need one?

You need an ATS when:

You can do without one when:

An ATS means standby duty: the machine stands idle and must start reliably when needed. This shifts the focus of the specification away from peak output and toward battery condition, a block heater in cold climates, and a monthly test run under load.

How it is wired: what connects to what

Buyers ask how an ATS connects more often than what it does. The layout is always the same, and it has four circuits, not one:

   Mains / utility ──────┐
                         ├──► [ ATS ] ──► Essential-loads panel
   Generator ────────────┘        │
                                  │ control cable (2 wires, dry contact)
                                  ▼
                          Generator controller
                            (remote-start terminals)
  1. Utility supply → the ATS “normal” input. This is the supply the ATS monitors.
  2. Generator output → the ATS “emergency” input. Size this cable for the ATS current rating, not for the generator’s kVA.
  3. ATS output → the essential-loads panel. Here you decide what is backed up. Transferring the whole distribution board usually costs more than a separate sub-panel for the loads that must never lose power.
  4. Control cable → the controller’s remote-start terminals. This is normally two wires and a dry (potential-free) contact. When the ATS closes the contact, the set starts. When it opens the contact, the set cools down and stops. This circuit makes the generator an automatic system, yet it is often missing from installation drawings.

Three details decide whether the installation works correctly:

A licensed electrician must install the ATS, following your local code. This section helps you read the quotation you receive and spot what is missing. It is not a guide to wiring a board connected to your service entrance yourself.

Three kinds of ATS, and which one to ask for

TypeHow it switchesWhere it fitsWhat to watch
Contactor-basedTwo interlocked contactorsSmall and mid-size installations; the usual choice at this power rangeNo short-circuit breaking capacity, so it needs upstream protection. It is the fastest and the least expensive
Motorised breakersCircuit breakers with a motor operatorLarge installations, high currentsBreaking capacity built in; slower (1–3 s more) and more expensive
Closed transitionOverlaps both sources for a few cycles, no breakLoads that cannot tolerate even a brief interruption when the grid returnsNeeds synchronisation and almost always the utility’s approval. Small sets usually cannot do it

For most standby installations of 5–100 kVA, the right choice is a contactor-based ATS with upstream protection. Closed transition for a telecom hut is more than the application needs.

What to specify when you order

Size an ATS for the load and the supply, not for the generator’s kVA. Give your supplier:

If the amp rating is right, most other choices follow from it. If it is wrong, the switch either trips without a fault or is oversized and costs more than necessary.

Testing the system

A standby set that has never been tested under load cannot be relied on. Run it every month, with load, long enough to reach operating temperature. Short, unloaded test runs cause wet-stacking: unburned fuel fouls the exhaust and the injectors, which is exactly the fault you do not want on the day the set is needed. The same efficient load range applies here as in any other duty; see fuel consumption per hour.

Check the battery at every test. A flat battery is the most common reason a standby generator fails to start, and it gives no warning before the moment it is needed.

Where HTX fits